Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

Minimum Order Quantity : 500meters Packaging Details : Iron-wooden drum
Delivery Time : 30days after payment Payment Terms : L/C, T/T
Place of Origin: Henan Brand Name: CN CABLE
Certification: CE Model Number: SHD-GC

Detail Information

Phase, Grounding Conductors, Ground Check Conductors:: Soft Or Annealed Tinned Coated Copper Conductor Shield:: A Helically Applied Semiconducting Tape
Insulation: EPR Insulation Shield: An Overlapped Semiconducting Tape Shall Be Applied Over The Insulation.
Metallic Component: A Composite Fiber-copper Braid Shield, Tinned Coated Copper Wires, Coverage Assembly:: Phase, Ground Check And Grounding Conductors Cabled Together With Hygroscopic Fillers And A
Ground Check:: Polypropylene Insulation Yellow Colored For Identification Jacket: CPE
High Light:

copper welding cable

,

special power cable

Product Description

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

 

APPLICATION
Trailing cable on ac mining equipment where service conditions are severe and maximum safety is mandatory; such as
power shovels and drag lines in open-pit mines, quarries, gantry cranes and slag reclaiming.
Used for high voltage distribution in underground mines where frequent relocation is necessary or where extra
flexibility and toughness is desired.
Meets all requirements of ICEA S-75-381.
CHARACTERISTIC
Excellent flexibility
Highly ozone, sun, weather and flame resistant
Excellent impact and abrasion resistant
Rated and flexible at -500C
Oil and heat resistant

 

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant 0

 

1. Phase, Grounding Conductors, Ground check conductors: Soft or annealed tinned coated copper
conductor, rope lay flexible stranding per ASTM B172
2. Conductor Shield: A helically applied semiconducting tape.
3. Insulation: High quality, heat, moisture, ozone and thermosetting ethylene propylene rubber (EPR)
meeting ICEA.
4. Insulation Shield: An overlapped semiconducting tape shall be applied over the insulation.
5. Metallic Component: A composite fiber-copper braid shield, tinned coated copper wires, Coverage
minimum 60 ,with colored fibers for phase identification (black, white, red).
6. Assembly: Phase, ground check and grounding conductors cabled together with hygroscopic fillers and a
binder tape.
7. Ground Check: Polypropylene insulation yellow colored for identification.
8. Jacket(CPE): Heavy duty or extra heavy duty chlorinated polyethylene (CPE) compound, applied in one
layer over a fibrous reinforcement layer, Black or other colors can be provided.
8. Jacket(TPU): Extra heavy duty, high torsion resistant, integral-filled, thermoplastic Polyurethane jacket,
Black or other colors can be provided.

 

Technical Data

SHD-GC 2 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductor Approximate overall
diameter
Ampacity
40°Cambient
temperature
Size Stranding
AWG or MCM   Inches Inches AWG   Inches A
6 133 7x19 0.070 0.155 10 49 7x7 1.26 93
4 259 7x37 0.070 0.155 8 133 7x19 1.36 122
2 259 7x37 0.070 0.170 6 133 7x19 1.55 159
1 259 7x37 0.080 0.170 5 133 7x19 1.71 184
1/0 266 19x14 0.080 0.190 4 259 7x37 1.81 211
2/0 342 19x18 0.080 0.205 3 259 7x39 1.94 243
3/0 418 19x22 0.080 0.205 2 259 7x37 2.07 279
4/0 532 19x28 0.080 0.220 1 259 7x37 2.24 321
250 627 19x33 0.095 0.220 1/0 266 19x14 2.44 355
300 740 37x20 0.095 0.235 1/0 266 19x14 2.70 395
350 888 37x24 0.095 0.235 2/0 342 19x18 2.73 435
500 1221 37x33 0.095 0.265 4/0 532 19x28 3.10 536

 

SHD-GC 5 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductor Approximate overall
diameter
Ampacity
40°Cambient
temperature
Size Stranding
AWG or MCM   Inches Inches AWG   Inches A
6 133 7x19 0.110 0.185 10 49 7x7 1.51 93
4 259 7x37 0.110 0.185 8 133 7x19 1.60 122
2 259 7x37 0.110 0.205 6 133 7x19 1.79 159
1 259 7x37 0.110 0.205 5 133 7x19 1.88 184
1/0 266 19x14 0.110 0.220 4 259 7x37 1.98 211
2/0 342 19x18 0.110 0.220 3 259 7x37 2.12 243
3/0 418 19x22 0.110 0.235 2 259 7x37 2.26 279
4/0 532 19x28 0.110 0.235 1 259 7x37 2.51 321
250 627 19x33 0.120 0.250 1/0 266 19x14 2.57 355
350 888 37x24 0.120 0.265 2/0 342 19x18 2.83 435
500 1221 37x33 0.120 0.280 4/0 532 19x28 3.18 536

 

SHD-GC 8 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductor Approximate overall
diameter
Ampacity
40°Cambient
temperature
Size Stranding
AWG or MCM   Inches Inches AWG   Inches A
4 259 7x37 0.150 0.205 8 133 7x19 1.93 93
2 259 7x37 0.150 0.220 6 133 7x19 2.02 122
1 259 7x37 0.150 0.220 5 133 7x19 2.10 159
1/0 266 19x14 0.150 0.220 4 259 7x37 2.21 184
2/0 342 19x18 0.150 0.235 3 259 7x37 2.34 211
3/0 418 19x22 0.150 0.250 2 259 7x37 4.49 243
4/0 532 19x28 0.150 0.250 1 259 7x37 2.63 279
250 627 19x33 0.150 0.250 1/0 266 19x14 2.75 321
350 888 37x24 0.150 0.280 2/0 342 19x18 3.05 355
500 1221 37x33 0.150 0.295 4/0 532 19x28 3.39 435

 

SHD-GC 15 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductor Approximate overall
diameter
Ampacity
40°Cambient
temperature
Size Stranding
AWG or MCM   Inches Inches AWG   Inches A
2 259 7x37 0.210 0.235 6 133 7x19 2.31 164
1 259 7x37 0.210 0.235 5 133 7x19 2.40 187
1/0 266 19x14 0.210 0.250 4 259 7x37 2.52 215
2/0 342 19x18 0.210 0.250 3 259 7x37 2.60 246
3/0 418 19x22 0.210 0.265 2 259 7x37 2.79 283
4/0 532 19x28 0.210 0.265 1 259 7x37 2.90 325
250* 627 19x33 0.210 0.265 1/0 266 19x14 3.05 355
350* 888 37x24 0.210 0.280 2/0 342 19x18 3.31 435
500* 1221 37x33 0.210 0.295 4/0 532 19x28 3.72 536

 

SHD-GC 25 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductor Approximate overall
diameter
Ampacity
40°Cambient
temperature
Size Stranding
AWG or MCM   Inches Inches AWG   Inches A
2 259 7x37 0.295 0.235 6 133 7x19 2.55 178
1 259 7x37 0.295 0.265 5 133 7x19 2.86 191
1/0 266 19x14 0.295 0.265 4 259 7x37 2.91 218
2/0 342 19x18 0.295 0.280 3 259 7x37 3.06 249
3/0 418 19X22 0.295 0.280 2 259 7x37 3.19 286
4/0 532 19x28 0.295 0.295 1 259 7x37 3.34 327
250* 627 19x33 0.295 0.295 1/0 266 19x14 3.43 360
350* 888 37x24 0.295 0.295 2/0 342 19x18 3.66 435

 